| Hydronics: |
|
|
| head (feet) / 2.31 = psi (water) |
2.31 ft. head = 1 psi |
|
| psi x 2.31 = head (feet) |
head (feet) x 0.433 = psi |
(note: 0.433 x 2.31 = 1) |
| Specific Gravity – 50% propylene glycol
mixture |
1.04 |
|
|
|
|
| Hydronics Rules of Thumb: |
(note: You can also ask
the plumbing supplier’s heat expert!) |
| Heat Delivery Flow Rate (water) |
F (gpm) =Boiler Rated Output 10,000 |
Glycol will increase flow requirement somewhat |
| Pump Head Requirement |
1. Measure longest run in ft. 2. Add 50% to that figure |
3. Multiply by .04 4. Result is pump head rqmt. |
| Max Flow Rate/Heat Carrying Capacity for
various CU pipe sizes |
1/2” - 1.5 gpm, 15K BTU 3/4” - 4 gpm, 40K BTU |
1” - 8 gpm, 80K BTU 1.25” - 14 gpm, 140K BTU |
|
|
|
| Copper: |
Gallons per Linear Foot (type”M”) |
|
| 1/2” |
.013 |
|
| 3/4” |
.027 |
|
| 1” |
.045 |
|
| 1-1/4” |
.068 |
|
| 1-1/2” |
.095 |
|
| 95%Tin 5% Antimony |
melting point
– 452 to 464 deg F. |
ASTM Alloy SB-5 |
| 50%Tin 50% Lead |
melting point
– 361 to 421 deg F. |
ASTM Alloy SN-50 |
| (95/5 Tin/copper |
melting point –440-500degF |
ASTM Alloy E |
| Tin/Antimony/Silver/Copper/
Nickel |
melting point –460-630degF. |
ASTM Alloy HB |
|
|
|
| PEX: |
Gallons per 100 Linear Ft |
Uponor HePex |
| 3/8” nominal |
0.50 |
|
| 1/2” |
0.01 (0.0098) |
|
| 5/8” |
0.02 |
|
| 3/4” |
0.03 |
|
| 1” |
0.04 |
|
| 1.25” |
0.05 |
estimated |
| 1.5” |
0.07 |
estimated |
|
|
|
| Propylene Glycol ( deg F): |
Freeze Protection Volume % |
Burst Protection Volume % |
| 0 |
36 |
24 |
| -10 |
42 |
28 |
| -20 |
46 |
30 |
| -30 |
50 |
33 |
| -40 |
54 |
35 |
The above from
DOWFROST HD
|
Solar
Energy
and
Radiant Heating Links:
|